Valve Sizing Data
Valve Sizing
Cv Defined
Valve Cv is the industry standard for valve capacity or flow characteristic. Cv is defined by the maximum flow of 60 Deg water expressed in GPM which produces a one PSI pressure drop across the valve.
Valve Sizing or cV Selection
For 2-Position “On-Off” Service and 3-Way Modulating Service, Select Line size or 10% of System Diff. Pressure for Delta P
For 2-Way Modulating (Throttle) Service, Select 50% of Gauge Inlet Pressure or 5 PSI Minimum for △P.
A modulating Butterfly Valve can be line size and meet the pressure drop requirement by specifying the maximum valve disc opening. Example—60% Maximum Disc Opening
Standard Valves
Cv Defined
Valve Cv is the industry standard for valve capacity or flow characteristic. Cv is defined by the maximum flow of 60 Deg water expressed in GPM which produces a one PSI pressure drop across the valve.
Valve Sizing or cV Selection
For 2-Position “On-Off” Service and 3-Way Modulating Service, Select Line size or 10% of System Diff. Pressure for Delta P
For 2-Way Modulating (Throttle) Service, Select 50% of Gauge Inlet Pressure or 5 PSI Minimum for △P.
A modulating Butterfly Valve can be line size and meet the pressure drop requirement by specifying the maximum valve disc opening. Example—60% Maximum Disc Opening
Formula for Fluids
Bray
download filePratt BF2-6888
download fileHigh Performance Valves
Cv Defined
Valve Cv is the industry standard for valve capacity or flow characteristic. Cv is defined by the maximum flow of 60 Deg water expressed in GPM which produces a one PSI pressure drop across the valve.
Valve Sizing or Cv Selection
For 2-Position “On-Off” Service and 3-Way Modulating Service, Select Line size or 10% of System Diff. Pressure for Delta P
For 2-Way Modulating (Throttle) Service, Select 50% of Gauge Inlet Pressure or 5 PSI Minimum for △P.
A modulating Butterfly Valve can be line size and meet the pressure drop requirement by specifying the maximum valve disc opening. Example—60% Maximum Disc Opening